15A, 20A, 30A
Repair or replace your UPS without power interruption by manually transferring critical loads from UPS power to utility power using the XBDM.
The XBDM ensures continuous uptime for your critical electronics. This maintenance bypass module allows you to manually transfer critical loads from UPS power to utility power using a bypass switch, enabling UPS repair or replacement without power interruption to the load. Transferring back to protected UPS power is just as easy; simply return the bypass switch to the UPS position.
[table colalign=”left|left|center|center|center|center|center “]
,MODEL NUMBER,XBDM-1015LV,XBDM-1020LV,XBDM-1030LV,XBDM-1020HV
POWER RATING,Voltage/current,120VAC/15A,120VAC/20A,120VAC/30A,230VAC/20A,120VAC/15A
INPUT,Utility input,”12 ft, 5–15P”,”12 ft, 5–20P”,”6 ft, L5–30P”,IEC C20
,AC frequency,50/60Hz,50/60Hz,50/60Hz,50/60Hz,50/60Hz
OUTPUT,Maximum output,12A,16A,24A,16A,15A
RECEPTACLES,Front output,(6) 5–15R,(6) 5–20R,(5) 5–20R,(2) C19 + (4) C13*
,Rear output,(4) 5–15R,(4) 5–20R,(5) 5–20R,(4) C13,(1) 5–15R
,Rear UPS input,(1) 5–15R,(1) 5–20R,(1) L5–30R,(1) C19,N/A
TRANSFER SWITCH,Quantity and capacity,(1) 15A,(1) 20A,(2) 20A,(1) 20A
UPS OUTPUT,Cord to UPS output,”3 ft, 5–15P”,”3 ft, 5–20P”,”3 ft, L5–30P”,IEC C20
AC SURGE,Max spike current,6500A,6500A,6500A,6500A
,Energy dissipation,114J,114J,114J,220J
,Max clamping voltage,330VAC,330VAC,330VAC,330VAC
INDICATORS,UPS available,Red LED[attr colspan=”3″]
,Utility available,Orange LED[attr colspan=”3″]
,Surge protection,Green LED[attr colspan=”3″]
PHYSICAL,Dimensions (W x D x H),17 x 3.5 x 1.75 in (1U)[attr colspan=”3″]
,Weight,3.5 lbs[attr colspan=”3″]
INCLUDED IN BOX,,”19 in rack mounting hardware, user manual, power cords (120VAC models)” [attr colspan=”3″]
[/table]