P91g Li Lithium Rack UPS – Online Double-Conversion (1500–3000 VA, 208–240V)

1500–3000 VA | 208–240 V | Online Double Conversion

Lithium rack UPS with online double-conversion topology for distributed IT, network closet, AV, and edge infrastructure. LiFePO₄ batteries deliver long lifecycle performance and high-temperature operation up to 50 °C.



1500–3000 VA · 208–240 VAC · Online Double-Conversion Lithium Rack UPS

P91g Li lithium online rack UPS

The P91g Li is a 2U online double-conversion UPS built on lithium iron phosphate (LiFePO₄) batteries for 208–240 V / global rack infrastructure. Online topology delivers zero transfer time and full isolation from upstream disturbances, while LiFePO₄ chemistry adds long service life, reduced maintenance, and fast recharge. Rack, tower, or wall mountable with IEC outlets and TAA compliance, it is the higher-voltage counterpart to the 120 V P91 Li.

1500–3000
VA (1350–2700 W)
208–240V
Single phase
Online
Double-conversion
LiFePO₄
Lithium iron phosphate
50°C
High-temp operation
6-year
Warranty (US & Canada)
Xtreme Power P91g Li 2U online double-conversion lithium rack UPS for 208-240V, front view with status LCD

P91g Li 2U online double-conversion lithium UPS — front view with 230 V status LCD.

Overview

Rack-level power continuity for 208–240 V infrastructure

The P91g Li is deployed in distributed infrastructure where localized UPS protection is required at the rack level and where higher-voltage operation is standard. Online double-conversion topology provides zero transfer time and continuous conditioned power independent of upstream disturbances, while lithium architecture reduces battery replacement frequency, improves thermal tolerance versus VRLA, and lowers lifecycle service requirements.

Need a 120 V version? The P91 Li is the 120 V counterpart with NEMA outlets and the same online lithium architecture.

P91 Li (120V) →

Key features

What the P91g Li delivers

Topology

Online double-conversion

Zero transfer time and the cleanest output – pure sine wave at ≤2% THD (linear) / ≤4% THD (non-linear), 0.9 output power factor.

Lithium

LiFePO₄ long life

Up to 15-year battery life or 3,000–5,000 discharge cycles, eliminating routine battery replacement.

Thermal

50 °C operation

Rated for high-temperature environments up to 50 °C (122 °F), with derating above 40 °C.

Protection

Battery management + hot-swappable battery

The battery management system provides cell balancing, current sharing, and over-charge / over-discharge protection; the hot-swappable battery pack is replaced without dropping the load, and the optional XBDM bypass lets the UPS itself be serviced or swapped.

Assurance

6-year warranty + $50,000 policy

Six years on electronics and battery in the USA and Canada (2 years depot repair outside), plus a $50,000 connected-equipment load protection policy in the USA and Canada when installed at 208 or 240V.

Efficiency

208–240 V, efficient, fast recharge

Selectable 200–240 VAC output; up to 98% ECO / 94% online efficiency; recharge to 90% in about 1.5 hours.

Where the P91g Li fits

The standard 208–240 V lithium rack platform

The P91g Li defines the standard 208–240 V lithium rack UPS tier within the Xtreme Power distributed infrastructure strategy. It is typically deployed in conventional rack layouts with external power distribution, sitting above the ultra-compact J60i and short-depth J60Ci, and below the high-density J90i.

Xtreme Power 208–240 V lithium rack architecture

Ultra-compact lithium
J60i
350–600 VA standby (230V)

View J60i →

Short-depth lithium
J60Ci
Shallow cabinet & wall-mount (230V)

View J60Ci →

Online rack lithium · this platform
P91g Li
2U online double-conversion, 230V

You are here

High-density lithium
J90i
1U, switching & extended runtime

View J90i →

P91g Li vs high-density lithium

P91g Li or J90i?

The P91g Li is the standard 2U platform for 208–240 V environments — built for internal-battery ride-through with conventional rack deployment and power distribution. The J90i delivers the same online lithium protection in a 1U chassis (half the rack height) and adds individual outlet control, plus external battery pack support on its 2kVA and 3kVA models for runtime well beyond what internal batteries alone provide. Choose the J90i when rack space is at a premium, outlet-level switching is required, or runtime must extend past the P91g Li’s internal-only configuration; choose the P91g Li when a standard 2U platform with internal runtime is the better fit.

Need a 1U footprint, outlet-level switching, or external battery packs for longer runtime? Compare the high-density J90i.

J90i →

Model selection

Three models, 1500–3000 VA

Model Capacity Receptacles Inlet / cord Dimensions (W×D×H) Weight Battery config
P91g-1.5kLi 1500 VA / 1350 W (8) IEC C13 C14 inlet · L6-20P, 8 ft 17.2 × 15.1 × 3.4 in 25.6 lbs 15S2P
P91g-2kLi 2000 VA / 1800 W (8) IEC C13 C14 inlet · L6-20P, 8 ft 17.2 × 19.0 × 3.4 in 33.5 lbs 15S2P ×2
P91g-3kLi 3000 VA / 2700 W (1) IEC C19 + (8) C13 C20 inlet · L6-20P, 8 ft 17.2 × 23.8 × 3.4 in 45.2 lbs 24S1P ×3

All models are 2U (3.4 in) high and 17.2 in wide. Rack depth is measured front bracket to unit panel; add 1 in for the front bezel. Output voltage is selectable (200 / 208 / 220 / 230 / 240 VAC); derate capacity to 80% at 200 or 208 VAC.

Battery runtimes

Internal battery runtime by load

Model 100VA
90W
150VA
135W
200VA
180W
300VA
270W
400VA
360W
600VA
540W
800VA
720W
1000VA
900W
1200VA
1080W
1400VA
1260W
1500VA
1350W
1600VA
1440W
1800VA
1620W
2000VA
1800W
2333VA
2100W
2666VA
2400W
3000VA
2700W
P91g-1.5kLi — 101 77 49 35 22 16 13 10 8 8 — — — — — —
P91g-2kLi — — 148 98 72 47 34 27 22 19 18 16 14 13 — — —
P91g-3kLi — — — 115 87 56 41 32 27 23 21 20 17 15 13 11 10

Approximate runtimes in minutes by absolute load — UPS load is shown in VA (top of each column) and watts (bottom, at 0.9 power factor). Each model is characterized from 10% to 100% of its rated load. Internal batteries only; actual runtime varies with battery age, temperature, and load profile. The P91g Li uses an internal battery architecture for ride-through and controlled shutdown — for extended runtime, the 1U J90i adds external battery packs on its 2k and 3k models. Size it with the UPS selector →

Applications

Built for global distributed infrastructure

The P91g Li is deployed across network closets, AV systems, telecommunications infrastructure, and distributed IT in 208–240 V environments — particularly IDF/MDF deployments and multi-site global infrastructure where a consistent, maintainable UPS platform is required.

Networking

Network closets

Conditioned 230 V power for switching, routing, and edge network equipment.

IDF / MDF

Distribution closets

A consistent lithium platform for IDF/MDF and structured cabling rooms.

Pro AV

AV systems

Clean, zero-transfer power for AV racks and control systems.

Telecom

Telecommunications

Reliable ride-through for telecom and communications nodes.

Edge IT

Distributed IT

Standardized rack protection across distributed and edge sites.

Global

Multi-site / global

Predictable lifecycle for repeatable 208–240 V deployments worldwide.

Capacity guidance: 1500 VA for network closets and distributed infrastructure; 2000 VA for IT racks and AV systems; 3000 VA for higher-density distributed environments.

Technical specifications

P91g Li specifications

Specification Detail
Topology Online double-conversion
Capacity 1500 / 2000 / 3000 VA (1350 / 1800 / 2700 W)
Output power factor 0.9
Input 110–300 VAC (load dependent), 50/60 Hz auto-sensing
Output voltage 200 / 208 / 220 / 230 / 240 VAC selectable (derate to 80% at 200 / 208 VAC)
Output waveform Pure sine wave; ≤2% THD (linear), ≤4% THD (non-linear)
Output frequency 50/60 Hz ± 0.1 Hz
Efficiency Up to 98% (ECO mode) / 94% (online mode)
Overload (online) 110–130% for 5 min; >130–140% for 30 s; >140% for 1.5 s
Battery LiFePO₄ (LFP26650, 2600 mAh cells); hot-swappable internal pack; battery management system (BMS)
Battery life Up to 15 years / 3,000–5,000 discharge cycles
Recharge 1.5 h to 90%; charger 2/4/6/8 A, LCD-adjustable
Form factor 2U; rack, tower, or wall mount
Operating temperature 32–122°F (0–50°C), derating above 104°F (40°C)
Altitude Up to 6,500 ft
Communications RS-232, USB, EPO; intelligent slot (Web/SNMP, relay/dry contact, Modbus)
Approvals CE, RoHS; battery packs UL1973, UN38.3; TAA compliant
Load protection policy $50,000 connected-equipment protection (USA and Canada, installed at 208 or 240V); registration required within 10 days of purchase
Warranty 6-year electronics / 6-year battery (USA and Canada); 2 years depot repair outside the USA and Canada
Included ViewPower software, front brackets, tower pedestals, user manual
Options Bypass distribution (XBDM), power distribution (XPDU), 4-post rail kit, 2-post shelf kit, wall-mount bracket

A 2-year warranty applies where ambient temperature exceeds 40°C (104°F) and is below 50°C (122°F). Confirm configuration-specific details on the datasheet.

Rack integration

Power distribution and maintenance bypass

The P91g Li is typically deployed with rack-mounted power distribution and external maintenance-bypass compatibility. An optional XPDU power-distribution unit and XBDM bypass module support standardized rack power architecture and let the UPS be serviced or replaced without interrupting the critical load.

Plan distribution, monitoring, and bypass as part of a standardized rack power architecture.

Rack power architecture →

Lithium lifecycle

Lifecycle advantages over VRLA

Lithium UPS systems provide lifecycle advantages over VRLA, including longer service intervals, improved thermal tolerance, and reduced maintenance intervention. The P91g Li’s LiFePO₄ architecture delivers up to 15-year battery design life, 3 to 4 times that of lead-acid, with faster recharge.

Compare lithium and lead-acid lifecycle, chemistry, and deployment trade-offs.

Lithium vs lead-acid →

Common questions

P91g Li — frequently asked questions

What is the difference between the P91g Li and the P91 Li?

Input voltage. The P91 Li is the 120 V platform with NEMA outlets; the P91g Li is the 208-240 V version with IEC outlets. Same 2U form factor, same LiFePO4 chemistry, same online double-conversion topology. Choose on the supply at the rack, not on features.

Should I specify the P91g Li or the J90i?

Rack space and runtime strategy. The P91g Li is the standard 2U platform built around internal-battery ride-through in conventional rack layouts. The J90i delivers the same online lithium protection in 1U, adds individual outlet switching, and supports external battery packs on its 2 kVA and 3 kVA models. Choose the J90i when rack space is tight, outlet-level switching is needed, or runtime must go beyond internal batteries. Choose the P91g Li when a standard 2U platform with internal runtime is the better fit.

Why does 50 degrees C matter?

Because most racks are not air conditioned. IDF closets, telecom rooms and industrial enclosures regularly sit at 35-40 C, and VRLA batteries specified at 25 C degrade rapidly above 30 C. The P91g Li is rated to 50 C with derating above 40 C, which covers the real range of deployment environments rather than the ideal one.

How long do the batteries last?

Up to 15 years or 3,000-5,000 discharge cycles. The practical comparison is against the 3 to 5 year VRLA replacement cycle. Across a distributed estate, removing that cycle removes both the parts cost and the site visit, and the visit is usually the larger number.

Can the batteries be replaced without dropping the load?

Yes. The internal battery pack is hot-swappable, and an optional XBDM bypass distribution module lets the UPS itself be serviced or swapped without interrupting the critical load. On a rack that cannot go down, the XBDM is usually specified with the UPS rather than added later.

What output voltage does it deliver?

200, 208, 220, 230 or 240 VAC, selectable. Note that capacity derates to 80% at 200 or 208 VAC, so size on the derated figure at the voltage you will actually run rather than on the nameplate.

Is the P91g Li TAA compliant?

Yes. Note that the certifications on this 208-240 V platform are CE and RoHS, with battery packs to UL1973 and UN38.3; there is no UL listing on this range. TAA compliance and safety listing are separate questions, and both matter on a regulated bid.

What is the warranty?

Six years on electronics and battery in the USA and Canada, reducing to two years where ambient temperature exceeds 40 C and is below 50 C, and two years depot repair outside the USA and Canada. In the USA and Canada, units installed at 208 or 240V carry a $50,000 connected-equipment load protection policy, with registration required within 10 days of purchase.

Plan with confidence

Xtreme Power supports consultants, facility engineers, and system integrators with lithium UPS deployment strategy, distributed infrastructure planning, and lifecycle modernization for 208–240 V environments.