700VA-3000VA
120VAC or 208/230VAC
An online tower UPS that provides protection against outages and downtime for critical electronic equipment.
The T90 provides clean reliable power with load segment control capabilities. The T90 is the perfect choice for critical business PCs, workstations, servers, IT equipment, communications systems, or networking equipment.
[table colalign=”left|left|center|center |center|center |center|center|center “]
,MODEL NUMBER,T90-700,T90-1000,T90-1500,T90-15HW,T90-2000,T90-3000,T90i-1500
INPUT,Capacity,700VA (490W),1000VA (700W),1500VA (1050W),1500VA (1050W),2000VA (1400W),3000VA (2100W),1500VA (1050W)
,Voltage range,60–144VAC**[attr colspan=”6″],120–276VAC**
,Frequency,50/60Hz auto sensing[attr colspan=”7″]
OUTPUT,Voltage,120VAC nominal (100/110/115/127VAC selectable)***[attr colspan=”6″],208/220/230/240VAC
,Waveform,”Sine wave, zero transfer time”[attr colspan=”7″]
,Frequency,50/60Hz auto sensing ≤ 1%[attr colspan=”7″]
,Load segments,Two controlled via software[attr colspan=”7″]
,Load power factor,0.7[attr colspan=”7″]
,Efficiency,”High efficiency > 95%, normal mode > 90%”[attr colspan=”7″]
,Overload capacity,”125% for 1 min, 150% for 10 sec”[attr colspan=”7″]
BATTERY,Battery type,(2) 12V7.2AH,(3) 12V7.2AH,(3) 12V9AH[attr colspan=”2″],(6) 12V7.2AH,(6) 12V9AH,(3) 12V9AH
,Recharge,4 hours to 90% capacity[attr colspan=”7″]
PHYSICAL,UPS dimensions (W x D x H),6.0 x 16.5 x 9.5 in[attr colspan=”4″],8.9 x 16.5 x 14.2 in[attr colspan=”2″],6.0 x 16.5 x 9.5 in
,UPS weight,31 lbs,38 lbs,39 lbs[attr colspan=”2″],73 lbs,78 lbs,39 lbs
,Line cord,5-15P*[attr colspan=”3″],Terminal block,5-20P*,L5-30P,IEC C14 inlet
,Receptacles,(6) NEMA 5–15R*[attr colspan=”3″],Terminal block,(12) NEMA 5–15/20R*,(10) NEMA 5–15R + (1) L5–30R,(4) IEC C13
,LCD display,”Input/output voltage, input/output frequency, online mode, backup mode, battery capacity, load level”[attr colspan=”7″]
OPTIONAL BATTERY PACKS,Model number,N/A,T90-BP/T90-BP1[attr colspan=”3″],T90-BP2[attr colspan=”2″],T90-BP/T90-BP1
,BP dimensions (W x D x H),N/A,BP – 6.0 x 16.5 x 9.5 in; BP1/BP2 – 8.9 x 16.7 x 14.2 in[attr colspan=”6″]
,BP weight,N/A,BP = 46 lbs; BP1/BP2 = 88 lbs[attr colspan=”6″]
,Battery type,N/A,BP – 2 x (3) 12V7.2AH; BP1 – 4 x (3) 12V7.2AH; BP2 – 2 x (6) 12V7.2AH[attr colspan=”6″]
ENVIRONMENT,Temperature,32–104°F (0–40°C) [attr colspan=”7″]
,Audible noise,< 40 dBA[attr colspan=”7″]
,Altitude,”11,500 ft above sea level”[attr colspan=”7″]
APPROVALS,,”UL, cUL, FCC, CE”[attr colspan=”7″]
WARRANTY,,”3 years electronics, 3 years battery warranty (USA and Canada)” [attr colspan=”7″]
COMMUNICATIONS INTERFACE,,”RS-232, USB, EPO, intelligent slot for optional cards (Web/SNMP, Relay/dry contact)” [attr colspan=”7″]
INCLUDED IN BOX,,”User manual, monitoring software, CD, USB cable”[attr colspan=”7″]
AVAILABLE OPTIONS,,”Extended warranty, bypass distribution (XBDM), power distribution (XPDU)” [attr colspan=”7″]
[/table]
*T90-2000 is also available with an L5–20P input and (1) L5–20R + (10) 5–15R output. **Depending on load level. ***T90 capacity derates 10% at 110VAC and 20% at 100VAC output voltage.
[table colwidth=”75″]
,Model,Description,Unit Weight, Unit Dimensions
,T90-BP,”Extended Battery Pack for T90-1000, T90-1500, T90i-1500 (2 strings)”,46 lbs,6.0″ x 16.5″ x 9.5″
,T90-BP1,”Extended Battery Pack for T90-1000, T90-1500, T90i-1500 (4 strings)”,92.4 lbs,8.9″ x 16.7″ x 14.2″
,T90-BP2,”Extended Battery Pack for T90-2000, T90-3000 (2 strings)”,92.4 lbs,8.9″ x 16.7″ x 14.2″
[/table]
[table colwidth=”75″]
,Model,Description,Unit Weight, Unit Dimensions
,T90-WMB,”Wall Mount Bracket for use with T90-700, T90-1000, T90-1500, T90-15HW, T90i-1500; Rated for 40 lbs”,5 lbs,4.0”-8.0” x 7.0” x 8.0”
[/table]
[table colwidth=”75″]
,Model,Description,Unit Weight, Unit Dimensions
,SNMP-1PIN,Internal Web/SNMP Card,1 lb,7.25″ x 6″ x 2.5″
,XPRT-RELAY,AS400 Dry Contact Interface Card,1 lb,7.25″ x 6″ x 2.5″
[/table]
[table colwidth=”75″]
,Model,Description,Utility Input, Output Connections, UPS Connections, Unit Weight, Unit Dimensions
,XBDM1020HV1,Bypass 16A capacity for use with T90i-1500 (includes IEC C20 C19 cord kit),”IEC C20 inlet”,”(2) IEC C19 + (4) IEC C13 front, (4) IEC C13 back”,IEC C20,3.5 lbs,19.3″ x 3.5″ x 1.75″
[/table]
[table colwidth=”75″]
,Model,Description,Input Power Cord, Outlets, Unit Weight, Unit Dimensions
,XPDU-IEC,230V Basic Power Distribution Unit for use with T90i-1500,IEC C20 inlet,(10) IEC C13 + (2) IEC C19,2.6 lbs,19.0″ x 3.5″ x 1.75″
,XPD-AT15A,1500W Transformer PDU with Meter 208V to 120V for use with T90i-1500,”Detachable IEC C14, 3ft”,(16) 5–15R,19.7 lbs,19.0” x 10.5” x 3.5”
,XAT-400,400VA Step Down Transformer 208V to 120V for use with T90i-1500,”208V IEC C14, 2ft”,”120V 5–15R, 2ft”,8.0 lbs,7.0” x 6.8” x 5.9”
[/table]