Product Snapshot

  • Capacity: 10kW
  • Up to 98% ECO mode or 94.5% online efficiency
  • Unity output power factor (kVA=kW)
  • Hardwired or cord/receptacle configurations
  • 2 years electronics, 2 years battery warranty (USA and Canada)

To receive a quote on M90C-2S UPS contact a sales representative at sales@xpcc.com

[table colalign=”left|left|center|”]

,MODEL NUMBER, M90C-2S

CAPACITY, Power Rating, 10kVA/10kW

INPUT,”Voltage/frequency nominal”, “380/220V, 400/230V, 415/240V three-phase, 50/60Hz auto-sensing” [attr colspan=”1″]

,”Voltage/frequency range”, “190-520VAC* (L-L) / 40–70Hz [attr colspan=”1”]

OUTPUT,”Voltage/Frequency”, “380/220V, 400/230V, 415/240V three-phase 50/60 Hz +/- 0.1Hz” [attr colspan=”1″]

,Efficiency,”98% ECO mode and 94.5% online mode”[attr colspan=”1″]

,Overload capacity,”100% – 110% for 30 min; 110% – 130% for 5min; 130% – 150% for 10s; > 150% for 200ms”[attr colspan=”1″]

BATTERY SYSTEM,Nominal voltage, “+/-192 or +/-240VDC (+/192V default)” [attr colspan=”1″]

,Max charging (adjustable),4A [attr colspan=”1″]

SYSTEM ENCLOSURE, Dimensions & Weight , 17.3”W x 31.5”D x 10.5”H (6U) / 34 lbs [attr colspan=”1″]

,Maximum Capacity  , 10kVA/10kW [attr colspan=”1″]

,Enclosure Capacity , 2 slots including 1 power module only slot + 1 battery module only slot [attr colspan=”1″]

,Output Connections , Hardwired or optional output cord/receptacles [attr colspan=”1″]

ENVIRONMENT,Temperature,0–40°C (32–104°F)** [attr colspan=”1″]

,Altitude, “1585 meters above sea level**” [attr colspan=”1″]

,Audible noise, < 58dBA at 1m [attr colspan=”1″]

APPROVALS,,”UL1778 Power Module, CE Pending [attr colspan=”2″]

WARRANTY,,”2 year warranty (USA and Canada)”[attr colspan=”2″]

COMMUNICATIONS INTERFACE,,”RS-232, USB, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus)” [attr colspan=”2″]

INCLUDED IN BOX,,”User manual, USB cable, RS-232 cable, ViewPower Software”[attr colspan=”2″]

AVAILABLE OPTIONS,,”Extended battery cabinet, caster base, 4-post rail kit “[attr colspan=”2”]

[/table]

*Depending on load level **Battery Life is reduced above 30°C, UPS Capacity derates above 30°C and 5,200 ft above sea level.