DX8-90 DC Power Shelf | 90 kW 800 VDC to 54 VDC Rack Converter

800 VDC to 54 VDC DC Power Shelf // 15 kW Hot-Swappable DC-DC PSU Modules

90 kW of 800 VDC to 54 VDC Power for AI Rack Infrastructure

Category:

AI Infrastructure Power // 800 VDC
PRELIMINARY — specifications subject to change

DX8-90: 800 VDC to 54 VDC at the rack, 90 kW per shelf

The DX8-90 is the stage that makes 800 VDC distribution usable at the server. It converts an 800 VDC bus into regulated 54 VDC at the rack, delivering up to 90 kW from six 15 kW hot-swappable DC-DC modules at above 98% efficiency. Each module shares current independently and can be added in 15 kW increments as rack load grows.

90 kW
Per shelf
800 → 54
VDC conversion
6 × 15 kW
Hot-swap modules
>98%
Efficiency, 50 to 80% load
300 A
Per module output
1 : 1
Pairs with AX8-110

Architecture

Why convert at the rack

Delivering 90 kW at 52 VDC from a central source would put about 1730 A on the full run into the rack. Converting at the rack instead keeps that current inside the shelf busbar, while the feed into the rack carries about 114 A at 800 VDC — the same power at about one fifteenth the current. Conductor loss scales with the square of current for a given cross-section.

FACILITY AC3-phaseAX8-110AC to 800 VDC800 VDC114 Arack feedDX8-90800 to 54 VDC90 kW, above 98%54 VDC1730 Ashelf busbarSERVERS54 VDCSame 90 kW, 15× less current on the run into the rackConductor loss scales with the square of current for a given cross-sectionCurrents shown at full 90 kW output

The 800 VDC power chain. The high-current path is confined to the DX8-90 shelf busbar.

Upstream: the AX8-110 converts three-phase AC into the 800 VDC bus — 110 kW from six 18.5 kW PSU modules, with optional LFP battery ride-through in the 7U AX8E-110.

AX8-110 →

System Design

One shelf, one rack

The DX8-90 pairs one-to-one with an AX8-110 or AX8E-110, connected directly with no intermediate PDU or bus. The 800 VDC input connector matches the output connector on the upstream shelf.

The capacity difference between the two is deliberate. A 110 kW upstream shelf feeding a 90 kW downstream load means five 18.5 kW PSU modules carry the load and the sixth is spare — module-level 5+1 redundancy across the pair, without a separate redundant shelf.

Sidecar rack

AX8-110 / AX8E-110

AC to 800 VDC conversion and, where specified, battery ride-through. Sits in the sidecar power rack alongside other shelves.

IT rack

DX8-90

800 VDC to 54 VDC conversion at the point of use. Sits in the IT rack with the compute it serves, keeping the high-current path as short as possible.

Key Features

What sets the DX8-90 apart

Density

90 kW per shelf
Six 15 kW DC-DC modules deliver high-density 54 VDC power in a 19-inch rack.
Efficiency

Above 98%
Above 98% efficiency from 50 to 80% load — less heat to remove at the rack.
Modularity

15 kW increments
Capacity scales module by module as rack load grows, without replacing the shelf.
Serviceability

Hot-swappable modules
Live serviceability keeps the shelf online during module replacement.
Scaling

Busbar current sharing
Modules and shelves share current on the 54 VDC rack busbar, each shelf fed by its own AX8-110.
Monitoring

Full telemetry
Voltage, current, temperature, fan speed, power, part and serial number, and black-box fault logging.

AI Infrastructure Power

Where the DX8-90 sits in the 800 VDC chain

800 VDC Power Chain

Source
FACILITY AC
415 / 480 VAC three-phase, two inputs
Rectification
AX8-110 / AX8E-110
110 kW AC to 800 VDC, optional battery ride-through
Conversion
DX8-90
90 kW 800 VDC to 54 VDC at the rack
Load
GPU / AI COMPUTE
54 VDC delivered at the rack

Specifications

Shelf and module

Parameter DX8-90
Shelf power rating 90 kW per shelf (6 × 15 kW)
Redundancy 90 kW (N+0) / 75 kW (N+1) / 45 kW (N+N)
Rated input voltage 800 VDC nominal; best efficiency at 790 to 800 VDC
Input voltage range 750 to 850 VDC
Input connection One DC input, matching the single 800 VDC output of the AX8-110. BizLink 117G0-178308-R1, 125 A rated; about 114 A at full load. 800 VDC, return, PE and an S1–S2 interlock loop closed inside the DX8-90, so the upstream shelf shuts down its output if the connector is unmated
Output voltage 54 to 52 VDC (54 V no-load, 52 V at 100% load; 2 V droop, 3 V at 150%). Fixed conversion ratio, not field-adjustable
Ripple and noise ±500 mV (20 MHz bandwidth)
Rated output current 300 A per module; 1800 A maximum per shelf
Shelf output connection Floating blind-mate connector, mates with ORv3 busbars. Liquid-cooled BarKlip termination not yet available; interim arrangement applies
Module rating 15 kW per DX8-150 module
Modules per shelf Up to 6
Efficiency Above 98% from 50 to 80% load
Current sharing Active current sharing
Hot swap Yes, front-serviceable
Module protection Over-voltage, over-current
Pulse load capability 180% for 0.5 ms; 150% for 50 ms; 100% continuous
Hold-up time 4 ms (ride-through provided by the upstream AX8E-110)
Parallel operation Within the shelf and between shelves on the 54 VDC rack busbar; each shelf fed by its own AX8-110. 800 VDC inputs are not paralleled

Communication and Control

Shelf to rack manager

The shelf’s Power Monitoring Controller connects over a gigabit Ethernet port to the top-of-rack switch and presents the shelf and its modules over DMTF Redfish. The same controller is used in the upstream AX8-110, so a single management system sees every shelf in the chain the same way.

Parameter DX8-90
Controller Power Monitoring Controller (PMC), shelf-level monitoring and control
Network 1 × gigabit Ethernet RJ45 to the top-of-rack switch
Management DMTF Redfish over HTTPS (PMC details)
Telemetry Voltage and current in and out, temperatures, fan speeds, power, serial and part number, hardware and firmware revision
Diagnostics Black-box fault logging

Mechanical and Environmental

Rack integration

DX8-90 shelf, front view showing six DX8-150 modules and the PMC slot
DX8-90 front view. Six DX8-150 15 kW modules with the Power Monitoring Controller at the left. Shelf in development; specifications preliminary.
DX8-90 shelf, rear oblique view showing the DC input connector
DX8-90 rear view. Single 800 VDC input from the upstream AX8-110.
DX8-150 15 kW DC-DC module, front view
DX8-150 15 kW DC-DC module, front. Hot-swappable and front-serviceable.
DX8-150 module, rear view showing the blind-mate connector
DX8-150 rear. Blind-mate Molex 2141150098-SD or equivalent.
Parameter DX8-90
Shelf dimensions 839.5 × 448 × 43.6 mm (D × W × H)
Shelf rack height 1U
Shelf weight 32 kg (70.5 lbs) populated; 8.5 kg (18.7 lbs) empty
Module dimensions (W × H × D) 66.7 × 40 × 701 mm
Auxiliary output 12 VDC / 1 A
Module I/O connector Molex 2141150098-SD or equivalent, blind-mate
Rack compatibility 19-inch EIA-310; fits 21-inch ORv3 racks with a mounting accessory
Rack placement IT rack, alongside the compute it serves
Operating temperature 5 to +45°C
Thermal behavior Over-temperature protection engages on sensor detection; no linear output derating
Humidity 8 to 85%, non-condensing
Operating altitude 3050 m (10,000 ft)
Acoustic noise Target not to exceed 95 dBA with fans at full speed (design target, not a measured figure)

Compliance and Safety

Standards

IEC / EN / UL 62368-1
EN 55032
EN 61000-3-11/-12
EN 61000-4-2/3/4/5/6/8/11

Environmental compliance marks are being consolidated into the shelf specification and will be published when the shelf termination is finalized.