JavaScript DHTML Menu Powered by Milonic
Description      Features Typical Applications      Specifications Included in the Box  

Xtreme Value Rack Tower Series (XVRT)
1000VA

 
XVRT-1000 SPECIFICATIONS


  US 120V Model DESCRIPTION

INPUT Voltage +/-25% at line input
 
  Capacity On Battery 1000VA/600W
 
  Surge Protection 500VA
 
  Frequency 50 / 60 Hz +/-10% auto sensing
 
  Frequency (on battery) 50 or 60 Hz +/-0.5%
 
  Voltage Regulation (AVR) AVR automatically increases output voltage 15% above input voltage if -9% to -25% of nominal. AVR decreases output voltage 13% below input voltage if +9% to +25% of nominal.
 
  Transfer Time 2/4 milliseconds, including detection time

PROTECTION Spike Protection 320 Joules, 2ms
AND
FILTERING EMI/RFI filter 10dB at 0.15MHz, 50dB at 30MHz
 
  Overload Protection UPS automatic shutdown if overload exceeds 110% of nominal at 60 seconds and 130% at 3 seconds
 
  Unit Input For overload & Short circuit protection
 
  10Base-T Cable Port Network (UTP, RJ-45) compatible jacks
 
  Short Circuit UPS output cut off immediately or input fuse protection

BATTERY Type Sealed, Maintenance-free lead acid
 
  Typical Recharge Time 8 hours (to 90% of full capacity)
 
  Protection Automatic self-test & discharge protection, Replace battery indicator
 
  Backup Time 3-180 min (depending on computer load)
 
  Communications Interface RS-232 Bi-directional communication port - Also, (1) RS232 to USB cable is provided to allow for USB connection/communications
 
  SNMP Connectivity Yes, via external SNMP card/device
 
  Recharge Time to 90% 8 hours

PHYSICAL Dimensions (W x D x H) 15.0" x 14.3" x 1.73"
 
  "U" Dimensions 1U
 
  Net Weight 25.3 lbs
 
  Gross Weight 28.6 lbs
 
  Line Cord 5-15P
 
  Receptacles NEMA 5 - 15 P (4)

ENVIRONMENT Maximum Ambient Temperature for Operation 0-35C for Ambient operation
 
  Audible Noise <45dba at one meter

WARRANTY Warranty Three years on electronics

APPROVALS North America UL cUL FCC

INDICATORS Battery Backup Slow beeping sound ( approx. 0.47 Hz)
AND ALARMS
  Battery Low Rapid beeping sound (approx. 1.824 Hz)
 
  Overload Continuous beeping sound

 

Xtreme value, Xtreme performance, Xtreme reliability

 

Products Navigation
Uninterruptible Power Supplies (UPS)
Line-Interactive UPS
Xtreme Value Tower Series (XVT)
Xtreme Value Rack Tower Series (XVRT)
  1000VA
  1500VA
  2200VA
  3000VA
On-line UPS
Bypass Distribution Modules
Power Distribution Unit
Downloads & Useful Information

  User's Manual (PDF)
  Product Brochure
    –  Black Background (PDF)

    –  White Background (PDF)
  Runtime Chart
  Product Photos
  Plug Types
Copyright © 2008 Xtreme Power Conversion Corporation. All rights reserved.          Terms of Use    |    Privacy Policy Get Adobe Acrobat ®    |    Site Map    |    Top of Page