RACKMOUNT (4U)
|
US 120V MODEL
|
DESCRIPTION
|
|
|
INPUT
|
Voltage
|
240/120V, 208/120V, 230/115V, 200/100V
|
| |
|
| |
Capacity (VA)
|
6000VA
|
| |
|
| |
Capacity (W)
|
4200W
|
| |
|
| |
Frequency
|
40-79 Hz
|
| |
|
| |
Power Factor
|
Greater than 0.97
|
| |
|
| |
Topology
|
True on-line, Double conversion, Input PF correction, auto bypass
|
|
|
OUTPUT
|
Voltage
|
240/120V, 208/120V, 230/115V, 200/100V (selectable) + 5%
|
| |
|
| |
Frequency
|
50/60 Hz auto sensing + 5% or Frequency Converter
|
| |
|
| |
Harmonic Distortion
|
< 3% with linear load; < 5% with non-linear load
|
| |
|
| |
Wave Form
|
Sine wave, zero transfer time
|
| |
|
| |
Efficiency AC/DC/AC
|
Greater than 86%
|
| |
|
| |
Auto Restart
|
Yes
|
| |
|
| |
Start on Battery
|
Yes
|
| |
|
| |
Overload Capacity
|
110% for 300 sec; 130% for 30 sec; 200% for 5 sec
|
| |
|
| |
Crest Factor
|
< 3 : 1 (full load(
|
|
|
BATTERY
|
Battery Type
|
(12) 8AH / 144VDC
|
| |
|
| |
Recharge Time
|
< 3 hours to 90%
|
| |
|
| |
Backup Time
|
UPS
|
14 / 5 (half load / full load)
|
| | (minutes) |
|
| |
+ (1) BP
|
34 / 14 (half load / full load)
|
| |
|
| |
+ (2) BP
|
58 / 25 (half load / full load)
|
| |
|
| |
+ (3) BP
|
82 / 36 (half load / full load)
|
| |
|
| |
+ (4) BP
|
105 / 47 (half load / full load)
|
|
|
PHYSICAL
|
Unit Dimensions (4U)
|
16.9"W x 22.5"D x 6.9"H
|
| |
|
| |
Unit Weight
|
162 lbs
|
| |
|
| |
Input Connection
|
L14-30P or Hardwire
|
| |
|
| |
Output Connection
|
(4) 5-20R + (1) L6-30R + (1) L14-30R or Hardwire
|
| |
|
| |
Communication Interface
|
RS-232 and USB standard, SNMP Communication (optional card)
|
| |
|
| |
Battery Pack Dimensions
|
16.9"W x 22.5"D x 3.5"H (2U)
|
| |
|
| |
Battery Pack Weight
|
95 lbs
|
|
|
ENVIRONMENT
|
Operating Temperature
|
0 - 40°C (32 - 104°F)
|
| |
|
| |
Audible Noise
|
< 55 dba
|
| |
|
| |
Altitude
|
11500 ft (3500 m) above sea level
|
|
|
WARRANTY
|
Warranty
|
Three years electronics / Three years batteries
|
|
|
APPROVALS
|
North America
|
UL cUL FCC
|