Capacity
|
3000VA/2400W
|
DESCRIPTION
|
|
|
INPUT
|
Phase
|
Single Phase Grounding
|
| |
|
| |
Voltage
|
115 - 295 VAC
|
| |
|
| |
Frequency
|
45Hz-55Hz@50hz / 55Hz-65Hz@60hz
|
| |
|
| |
Power Factor
|
≥ 0.98
|
| |
|
| |
Bypass Voltage Range
|
186VAC - 252VAC
|
| |
|
| |
Harmonic Distrotion
|
< 5% Non-Linear Load
|
|
|
OUTPUT
|
Phase
|
Single Phase Ground
|
| |
|
| |
Rated Voltage
|
208/220/230/240VAC
|
| |
|
| |
Power Factor
|
0.8
|
| |
|
| |
Voltage
|
± 2%
|
| |
|
| |
Frequency
|
50/60 HZ ± 0.2
|
| |
|
| |
Crest Factor
|
3:1
|
| |
|
| |
Transfer Time
|
0 ms
|
| |
|
| |
Overload Capacity
|
150% for 30 sec; 200% for 300ms
|
| |
|
| |
Efficiency AC/DC/AC
|
≥ 90%
|
|
|
BATTERY
|
Voltage
|
72VDC
|
| |
|
| |
Holdover Time
|
5 Minutes Full Load; 12 Minutes Half Load
|
| |
|
| |
Charge Current
|
1A
|
| |
|
| |
EBP Batteries
|
(2) Strings of (6) 12V 9AH
|
|
|
Communications Interface
|
|
RS232, USB, Dry Contact, SNMP (Optional)
|
|
|
Included With Unit
|
|
RS232, Software, Cable, Mounting Brackets, User's Manual, Input Power Cord
|
|
|
PHYSICAL
|
Unit / Shipping Dimensions W x D x H (mm)
|
440 x 520 x 131 / 607 x 654 x 210
|
| |
|
| |
Unit / Shipping Weight (Kg)
|
26 / 28.8
|
| |
|
| |
Input Power Cord
|
IEC to 1.8m length, British input plug, 1.5x3C OD8.5mm
|
| |
|
| |
Receptacles
|
(4) IEC C13 + (1) IEC C19
|
| |
|
| |
Unit / Shipping EBP Dimensions W x D x H (mm)
|
EBP3 440 x 520 x 131 / 607 x 514 x 170
|
| |
|
| |
Unit / Shipping EBP Weights (Kg)
|
41 / 43.8
|
|
|
ENVIRONMENT
|
Temperature
|
0 - 40°C
|
| |
|
| |
Humidity
|
0 - 95% Non-Condensing
|
| |
|
| |
Altitude
|
< 1500m
|
|
|
APPROVALS
|
|